Motor Speed & VFD Calculator

AC induction motor speed from poles and frequency, slip from the nameplate, and what happens to speed, torque, power and voltage when a frequency inverter (VFD) runs the motor slower or faster.

Mains frequency
Motor poles
RPM
kW
From the motor nameplate. Rated speed is always a little below the synchronous speed; the difference is the slip.
V
VFD output frequency
50 Hz
Hz
Load
Field turns at synchronous speed, rotor slips behind

Speed table

Synchronous and typical full-load speed for each pole count at the selected mains frequency, and at common VFD frequencies.

How it is calculated

Three-phase induction motor on a V/f frequency inverter. p is the number of poles (not pole pairs), f the frequency, s the slip. Base frequency is the mains frequency on the nameplate.

Synchronous speed ns = 120 · f / p Slip s = (ns − n) / ns, slip speed Δn = ns − n Rated torque T = 9549 · P / n (N·m, kW, RPM) Speed on VFD n ≈ 120 · f / p − Δn · (T_load / T_rated) Below base freq. V = V_rated · f / f_base, torque available = T_rated (constant torque) Above base freq. V = V_rated, torque available ≈ T_rated · f_base / f (constant power) Fan or pump T ∝ n², P ∝ n³

Rules of thumb for the warnings: a self-cooled motor at full torque below about 20–25 Hz gets too hot, because its own fan slows down; above about 1.5 × base frequency check the bearings, balance and the maker's mechanical speed limit; for fans and pumps the power rises with the cube of speed, so running faster than rated quickly overloads the motor.